Nile Deployment Readiness Template
Overview
The document outlines a comprehensive checklist for site readiness and configuration Readiness, especially focusing on IT closet infrastructure.
Site Readiness
It provides detailed recommendations regarding closet size, construction materials, cooling requirements, power specifications, and rack installations to ensure optimal operations. The checklist includes various closet sizes suitable for different areas, emphasizes a robust cooling system with specific temperature and humidity controls, and mandates dual redundant power setups. Additionally, it details requirements for power distribution and rack configurations, ensuring adequate airflow and grounding.Cabling considerations emphasize the installation of high-quality cables, termination standards, and maintaining clean and accessible cable trays.
Migration and Configuration Readiness
Migration and configuration readiness checklist provides details processes and comprehensive network design. It also includes necessary information for settings such as DHCP and wireless SSID configurations, along with supported firewall vendors.
Ultimately, these guidelines aim to facilitate a functional and efficient IT environment ready for Nile Access Service deployment.
Site Readiness
IT Infrastructure Checklist
Closet
Please consider physical environment, functional space and other considerations to right size closet area. You may refer to the industry standard recomendations such as BICSI for right-sizing the closet.
Closet Size
Closet size of 5’x7’ feet to serve up to 5,000 sq. ft.
Closet size of 6’x9’ feet to serve up to 10,000 sq. ft.
Closet size of 8’x12’ feet to serve up to 20,000 sq. ft.
Closet Room Construction Material
Interior walls: Insulated steel frame with gypsum board
Floor: 4-inch concrete slab
Ceiling: ½ inch acoustic tiles
Exterior walls: Insulated concrete with foam sheathing
Closet Cooling
Dedicated Cooling
High efficiency cooling system (7x24)
Redundant cooling system in place
Operates in low ambient temperature (0°F)
Cooling capacity reviewed (1-3 Ton = 3.4-10 kW)
Capacity
Minimum 1 Ton = 12,000 BTUH = 3.4 kW
Maximum 3 Ton = 36,000 BTUH = 10 kW
Room temperature range maintained (72–80°F)
Room humidity maintained at 50%
Cooling Type
House Air
Exhaust Fan
Rack Cooler
Mini Split
Ceiling Split
Airflow Clearance
Minimum 2 feet airflow clearance front and back of racks
Power
1100 W dual redundant power supported
UPS Readiness
UPS size between 1 kW and 10 kW
UPS Type: Line Interactive / On-Line (recommended)
Clean and well-regulated power source
Pure Sine Wave Output UPS selected to ensure the UPS provides a pure sine wave output (not simulated or approximated).
Avoid Stepped Approximation or Simulated Sine Wave UPS ( Do not use "stepped approximation" or "simulated sinewave" UPS models, as they can cause instability or equipment malfunction. )
UPS Capacity matches NSB power requirements ( Confirm the UPS is rated for the full load of the NSB installation, including any PoE-powered devices. )
UPS runtime supports graceful shutdown or failover ( Ensure the backup power duration meets operational needs or failover time thresholds.)
Regular UPS health check scheduled (Add periodic checks to verify battery health and proper waveform output.)
Battery backup for 4 to 10 minutes
Backup generator available.
Power redundancy
Centralized
Distributed
Power Distribution
High-quality PDU installed
Data center power products include upgradeable power distribution units, inline power meters, transfer switches and monitoring sensors
Inline power meters present
Transfer switches <10 ms transfer time
Monitoring sensors installed
Single/Redundant power strips used
Racks
4-Post Racks (Standard 19” Equipment Front Panel, 18 – 5/16” Center to center, 17-3/4th minimum opening) installed
2-Post rack used where applicable (45U)
Rack is grounded using ground lug
If the rack is not grounded or cannot be grounded, the switch is grounded directly by means of the provided ground lug
4 feet distance maintained between racks in multi-rack install to prevent switches/Head Ends (HE) from drawing in the hot air exhausted by another switch/HE
Rackmount UPS
Rackmount UPS supports extended battery module
Wall-Mount Rack Enclosures
Wall-mount rack (4-Post 12U or 6U) installed where needed
Rackmount PDUs
Rackmount PDU installed (Horizontal/Vertical)
Reference Nile Devices Physical and Environmental Specification
Feature\Nile Device Model | NSW200 | NSW250 | NSW1000 | NSW1500 | NHE1000 |
|---|---|---|---|---|---|
Physical dimensions | 440mm x 350mm x 44mm | 433mm X 425mm X 44.3mm | 433mm x 410mm x 43.5mm | 433mm x 410mm x 43.5mm | 437mm x 504mm x 43mm |
| 17.3” x 13.8” x 1.73” (WxDxH) | 17” X 16.7” X 1.74” (W X D X H) | 17” x 16.1” x 1.7” (W x D x H) | 17” x 16.1” x 1.7” (W x D x H) | 17.2in x 19.85in x 1.7in (W x D x H) |
Weight | 6.74 kg | Switch+Tray+PSU – 8.9 kg | 15.05 kg | 14.77 kg | 8 kg |
Operating temperature | 0~45 °C | 0~45 °C | 0~45 °C | 0~45 °C | 10°C to 35°C with RH 90% |
Operating altitude | 10000ft | 10000ft | 10000ft | 10000ft | 10000ft (not given in spec) |
Operating humidity | 85% (non-condensing) | 85% (non-condensing) | 85% (non-condensing) | 85% (non-condensing) | 90% (non-condensing) |
Storage temperature and humidity | -40°C to 70°C with RH 95% | -40°C to 70°C with RH 95% | -40℃ to 70℃ with RH 95% | -40℃ to 70℃ with RH 95% | -40°C to 70°C with 95% RH |
Operating Power | 150W (excluding PoE) | 300W (including PoE) | 391W (excluding PoE) | 412W | 303W |
Mounting requirements | 2 Post Net Rack, 1U | 2 Post/ 4 Post Net Rack, Wall mount | 2 Post/ 4 Post Net Rack, 1U | 2 Post/ 4 Post Net Rack, 1U | 2 Post/ 4 Post Net Rack, 1U |
Rack requirements | Standard 19-inches rack | Standard 19-inches rack | Standard 19-inches rack | Standard 19-inches rack | Standard 19-inches rack |
PoE (PSE) Budget | 850W (Redundant) | 150W (non-redundant) | 650W (redundant) | | |
Airflow | Front to Back | Front to Back | Front to Back | Front to Back | Front to Back |
PSU / Power source | 1000W (110VAC) 1200W (230VAC) Dual redundant | 300W external Power supply (non-redundant) | 1100W dual redundant | 550W dual redundant | 400W dual redundant |
Cabling Checklist
Nile Equipment Interconnect | Recommendation | Checklist |
|---|---|---|
Nile Access Switching to Nile Access Point | Installed up to 300 linear feet (Indoor / Outdoor) CAT6A Plenum rated shielded cable for Indoor / Non-Plenum rated shielded cable for Outdoor. Left 10 linear feet of cable length coiled up near the Access Point location. For reliable operation and connectivity via BLE, please ensure that the distance from the device is less than 30ft. | ☐ |
Nile Access Switching to Nile Distribution Switching | Used OM4 or OS2 | ☐ |
Nile Access Switching to Client | Used Cat5e or higher for 1 GbE | ☐ |
Nile Gateway to Customer Router /Firewall | Used Cat6a for 1 Gbe | ☐ |
Nile Gateway to Customer Router /Firewall | Used OM4/OS2 for 10GbE | ☐ |
Patch Panels and Patch Cables Checklist
Quality Cables Installed
Quality Terminations
Cable Length Slack provided
Quality Patch Panel installed
Patch Cables Length installed as Required
Cable Tray Checklist
Clean, Visible, and Non-blocking Air Flow and LED Access
No Overloaded Cable Trays
No Sharp Bending of Ethernet and Fiber Cables
Minimum Bend Radius for Copper Cable: 5x Outer Diameter (OD) ensured
Minimum Bend Radius for Fiber Cable: 10x Outer Diameter (OD) ensured
Migration & Configuration Readiness
Migration Checklist
Settings | Checklist |
|---|---|
Migration Process and StrategiesMigration Process and Strategy | ☐ |
Migration TopologiesMigration Topologies | ☐ |
Settings Checklist
Settings | Checklist |
|---|---|
☐ | |
☐ | |
Setup DHCPSetup DHCP | ☐ |
Setup AuthenticationSetup Authentication | ☐ |
Setup Guest PortalSetup Guest Portal | ☐ |
Setup SegmentsSetup Segments | ☐ |
Setup Wireless/SSIDSetup Wireless/SSID | ☐ |
Setup MAC AuthenticationSetup MAC Authentication | ☐ |
Configure AlertsConfigure Alerts | ☐ |
☐ |
Supported Firewall Checklist
Vendor | Checklist |
|---|---|
Meraki | ☐ |
Palo Alto | ☐ |
Fortinet | ☐ |
Juniper | ☐ |
Cisco | ☐ |
Nexus | ☐ |
Velo Cloud | ☐ |
Sophos | ☐ |